dc.description.abstract |
Series of blackouts encountered in recent years in power system have been occurred because either of voltage or angle instability or both together was not detected within time and progressive voltage or angle instability further degraded the system condition, because of increase in loading. This paper presents the real-time assessment methodology of voltage stability using Phasor Measurement Unit (PMU) with observability of load buses only in power network. PMUs are placed at strategically obtained location such that minimum number of PMU’s can make all load buses observable. Data obtained by PMU’s are used for voltage stability assessment with the help of successive change in the angle of bus voltage with respect to incremental load, which is used as on-line voltage stability predictor (VSP). The real-time voltage phasors obtained by PMU’s are used as real time voltage stability indicator. The case study has been carried out on IEEE-14 bus system and IEEE-30 bus systems to demonstrate the results. © 2017 Institute of Advanced Engineering and Science. All rights reserved. |